Learning, Circuit,

Can Two Circuits Share a Neutral?

When it comes to home wiring, is it possible to have two circuits sharing a neutral? We go into more detail and explain.

Neutral wires are sometimes shared for convenience and savings, as it is technically possible. But it is not a recommended practice and is probably not permitted by your local codes. There are several disadvantages to sharing it. You won’t be able to use an AFCI or GFCI on such a circuit, it can create a risk of electrocution and fire due to high current flow, and current may still flow while switched off at the panel, unless a two-pole breaker is used.

Situations in which Circuits can Share a Neutral

There are certain situations in which a shared neutral (multi-wire branching) is not uncommon.

One such situation is a multi-wire branch circuit in which two live wires share a single neutral. It might be seen, for example, in some kitchens and older houses. This arrangement is usually made to save on the copper wiring and keep the number of electrical wires to a minimum.

Regardless, this effect is that you get two circuits at one point. This circuit arrangement is called a multiwire branch circuit, which is defined as (for a single phase):

“A branch circuit with two or more circuit phase conductors having a voltage between them, with equal voltage between each phase conductor and the neutral conductor.”

branch circuit multiwire
Video | Mike Holt NEC


What You Should Do If You Share a Neutral

If you have the situation described above where a neutral is being shared, you must adjust the main panel.

Because two circuits are involved in a shared neutral situation, you should bond the two circuit breakers for those circuits. This is necessary to ensure both are either on or off simultaneously. It should not be possible for only one or the other to be on or off.

To be extra safe, if both circuit breakers are in the off position, don’t automatically assume there is no voltage in the two circuits. You should test them so that neither is life.

Warning: The risk of sharing a neutral is when the circuits sharing it are disconnected. While this is done, and they are not properly disconnected, the appliances on those circuits could get damaged, and the wiring can catch fire. Therefore, both circuit branches must be disconnected simultaneously.

Places that share a neutral, for example, to reduce wiring, usually have more than one ungrounded conductor to support multi-branching.

Installing a Two-Pole Circuit Breaker

CliNT circuit breaker

Installing a two-pole circuit breaker might be a good idea when sharing a neutral.

The two connected circuits will be treated as two separate branches or legs of a single circuit by installing a two-pole circuit breaker. Also, you can easily switch the whole two-branch circuit on and off with a single breaker. This is better than sharing a neutral or bonding the two circuit breakers.

Another important advantage of using a two-pole circuit breaker is that the single circuit breaker will not allow a current higher than the current rating for that breaker.

For example, if the two legs draw the same current, say 6A each, then no current will pass through the neutral. But if one draws, say, 6A, and the other draws 3A, then the difference of 3A will be returned through the neutral. This happens because the current takes the path with the lowest impedance (shortest conductor).

Warning: If sharing a neutral on the same leg using two circuit breakers, the return current could get quite high. If this current exceeds what the wires can tolerate, this situation could create a fire hazard.


FAQs

Why is a neutral connection even necessary?

Neutral connections in our AC electrical circuits are necessary to complete them. They provide a pathway for the current to return, enabling the switch to retain power while turned off. Without it, the current breaks and cannot return to its source, which could cause a high accumulation of electrical charge.

How many circuits can share a neutral?

Technically, you can share up to 3 circuits on a single neutral wire if you have a 3 phase system. In this case, you will need to bind the three circuit breakers together.

What type of circuits can or cannot share a neutral?

It is best NOT to share a neutral if the two circuits are dissimilar. The risk, again, is if one circuit is opened and the other is closed, as this would still allow electricity to pass through the combined circuit.

What does the NEC code have to say about sharing a neutral?

The NEC code does not permit sharing a neutral.

Can circuits share multiple neutrals?

It is also technically possible for electrical circuits to share multiple neutral wires, but this is not recommended. There will likely be a difference in current flows between them. Also, never tie different neutrals together. Otherwise, the current overload could cause a fire outbreak. If you need to do this, it must only be done at the panel where the circuit is completed.


Disadvantages of Sharing a Neutral

After reading this far, you may have gathered that although it is possible to share a neutral, it is not recommended. These are the main reasons why:

  • This is an old way of saving copper and minimizing wiring, which is no longer regarded as good practice.
  • If both connected circuits are not closed or turned off together, there will still be current in them.
  • You will not be able to use an AFCI or GFCI on a shared neutral circuit.
  • Magnetic field imbalance – see below.

In short, sharing a neutral is not recommended due to high current, electrocution, and potentially a fire risk. For safety reasons, using only one neutral per circuit is best.

Magnetic Field

Another reason why sharing a neutral would not be a good idea. It is to do with the magnetic field.

As long as the share neutral is in the same conduit as the two current-carrying wires, this is not another problem, but there might be a situation where it is not together. In this case, the magnetic field around the live wires will not get canceled. A magnetic field will remain around the live wires.

Consequently, if the live wires are in a steel conduit, they could become life, and if they are in a plastic conduit, it could potentially lead to a fire outbreak.


Sharing a Neutral Safely

After reading the above recommendations not to share a neutral, you still want to do so; here are some tips for doing it safely to minimize the risks.

As per NEC 2020 210.4(A-D), when setting up a multiwire branch circuit:

  • (A) Ensure that all conductors originate from the same main panel.
  • (B) Ensure there is a way to disconnect all phase conductors simultaneously where the circuit originates.
  • (C) Only use each circuit to supply one piece of equipment.
  • (D) Use cable ties or another way to identify the grouped wires.

multiwire branch circuits general
Video | Mike Holt NEC

multiwire branch circuit
Video | Mike Holt NEC

multiwire circuits grouping
Video | Mike Holt NEC

Take a look at some of our related articles below.




Video Reference

Mike Holt NEC

How helpful was this article?

Were Sorry This Was Not Helpful!

Let us improve this post!

Please Tell Us How We Can Improve This Article.

About Sam Orlovsky

AvatarCertifications: B.E.E.
Education: University Of Denver - Electric Engineering
Lives In: Denver Colorado

Electrical engineering is my passion, and I’ve been in the industry for over 20 years. This gives me a unique ability to give you expert home improvement and DIY recommendations. I’m not only an electrician, but I also like machinery and anything to do with carpentry. One of my career paths started as a general handyman, so I also have a lot of experience with home improvement I love to share.

| Reach Me

Leave a Comment